Customization: | Available |
---|---|
Application: | Insulators, Electrical Winding Insulation, Winding Wire Coating Insulation, Electrical Base, Shell, Motor, Insulating Varnish, Switch Baseplate |
Color: | Black |
Still deciding? Get samples of US$ 0/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Product: Cross-linked Polyolefin Cable Breakout Boots
Material: polyolefin
Shrink temperature: Start at 100ºC, and shrink totally at 130ºC
Voltage Rating: up to 35KV
Color: Black, red, milk-white(only for oil-resistant terminations)
CharacteristicsSpecification | Cable Specification | As supplied(mm) | Full Length | After Recovery(mm) | ||||
Breakout Main Diameter | Finger Diameter | Breakout Main Diameter | Finger Diameter | |||||
2 Cores Breakout | 0# | 1kv | 4-6,10-16 | ≥24 | ≥12 | 130±5 | ≤12 | ≤6 |
1# | 25-50 | ≥40 | ≥20 | 140±5 | ≤14 | ≤8 | ||
2# | 70-120 | ≥48 | ≥25 | 145±5 | ≤17 | ≤8 | ||
3# | 150-240 | ≥63 | ≥35 | 135±5 | ≤25 | ≤12 | ||
4# | 300-400 | ≥74 | ≥40 | 140±5 | ≤25 | ≤12 | ||
3 Cores Breakout | -2# | 4-6,10-16 | ≥28 | ≥11 | 130±5 | ≤17 | ≤6 | |
-1# | 25-50 | ≥48 | ≥18 | 170±5 | ≤22 | ≤8 | ||
0# | 70-120 | ≥60 | ≥25 | 175±5 | ≤28 | ≤9 | ||
1# | 10kv | 25-50* | ≥70 | ≥30 | 225±5 | ≤36 | ≤14 | |
2# | 70-120* | ≥85 | ≥39 | 235±5 | ≤45 | ≤16 | ||
3# | 150-240* | ≥105 | ≥42 | 245±5 | ≤53 | ≤19 | ||
4# | 300-400* | ≥125 | ≥58 | 245±5 | ≤63 | ≤25 | ||
5# | 300-500* | ≥140 | ≥65 | 245±5 | ≤63 | ≤25 | ||
4 Cores Breakout | 0# | 1kv | 4-6,10-16 | ≥38 | ≥10 | 130±5 | ≤18 | ≤6 |
1# | 25-50 | ≥50 | ≥16 | 135±5 | ≤24 | ≤7 | ||
2# | 70-120 | ≥68 | ≥23 | 180±5 | ≤32 | ≤9 | ||
3# | 150-240 | ≥80 | ≥30 | 210±5 | ≤44 | ≤13 | ||
4# | 300-400 | ≥90 | ≥35 | 210±5 | ≤44 | ≤13 | ||
5# | 500-630 | ≥110 | ≥40 | 210±5 | ≤44 | ≤13 | ||
5 Cores Breakout | 0# | 4-6,10-16 | ≥42 | ≥12 | 155±5 | ≤21 | ≤5 | |
1# | 25-50 | ≥55 | ≥15 | 170±5 | ≤29 | ≤7 | ||
2# | 70-120 | ≥70 | ≥23 | 170±5 | ≤38 | ≤10 | ||
3# | 150-240 | ≥90 | ≥30 | 180±5 | ≤51 | ≤13 | ||
4# | 300-400 | ≥120 | ≥39 | 205±5 | ≤47 | ≤14 |
Property | Test Method | Standard |
Operating Temperature | IEC 216 | -40ºC ~ +105ºC |
Tensile Strength | GB1040 | ≥12MPa |
Breakage Elongation(%) | GB1040 | ≥300% |
Breakdown Strength | GB1408 | ≥15kV/mm |
Volume Resistivity | GB1410 | ≥1×1011.m |
Brittle Temperature | GB5470 | ≤-40ºC |